                Titel:
             | 
        
        
            | 
                Photovoltaic noise barrier at the A9-highway in the Netherlands : results of the monitoring programme
             | 
        
        
            | 
                 
             | 
        
        
            | 
                Auteur(s):
             | 
        
        
            | 
                
             | 
        
        
            | 
                 
             | 
        
        
            | 
                Gepubliceerd door:
             | 
            
                Publicatie datum:
             | 
        
        
            | 
                ECN
                Zonne-energie
             | 
            
                1-2-2001
             | 
        
        
            | 
                 
             | 
        
        
            | 
                ECN publicatienummer:
             | 
            
                Publicatie type:
             | 
        
        
            | 
                ECN-C--01-021
             | 
            
                ECN rapport
             | 
        
        
            | 
                 
             | 
        
        
            | 
                Aantal pagina's:
             | 
            
                Volledige tekst:
             | 
        
        
            | 
                41
             | 
            
                Download PDF
                 (6475kB)
             | 
        
    
    
    
        Samenvatting:
        A large photovoltaic (PV) energy system has been integrated into a noise  barrier at the A9-highway near Ouderkerk aan de Amstel. Netherlands. The PV-system consists of 720 AC-modules with inverters of type A and 1440 AC-modules with inverters of type B. The monitoring activities within the project are performed by ECN in co-operation with Fraunhofer ISE, Germany. This document describes the results of the monitoring programme during the first 2 years of operation. The main conclusions are: (1) The AC-modules with type A inverters perform very well and have a low failure rate; (2) The AC-modules with type B inverters perform less good and have a higher failure rate. The reasons of the lower performance are the lower inverter efficiency and the occurrence of grid interference. Modifications on the PV-system to prevent the grid interference are ongoing; and (3) Accumulated traffic dust on the modules causes significant energy losses. The main recommendations are: (1) Global monitoring should be continued for the assessment of the results of the modifications and for detecting possible failures in the future; and (2) Annual cleaning of the modules after the winter season should be considered. (4 refs.)
    
    
        
        
    
    