Titel:
|
Gedrag van het PV-systeem op Houttuinen Zuid 41 te Apeldoorn
|
|
Auteur(s):
|
|
|
Gepubliceerd door:
|
Publicatie datum:
|
ECN
|
1998
|
|
ECN publicatienummer:
|
Publicatie type:
|
ECN-C--98-001
|
ECN rapport
|
|
Aantal pagina's:
|
Volledige tekst:
|
34
|
Download PDF
(838kB)
|
Samenvatting:
In this first progress report of the analytical monitoring of the titlesystem the results of the measurements in the period 5 September 1997 - 1 December 1997 are presented. During the measuring period the photovoltaic
(PV) system did not break down. The nominal capacity of the 44 PV-modules is
2090 Wp. The inverter capacity is 1500 W, which is underdimensioned. In case
of high solar radiation the generated capacities do not correlate with the
intensity of the solar radiation because of the limited inverter capacity.
The annual energy yield is 2.1% lower compared to a non-underdimensioned
inverter. The performance ratio is circa 0.81. The average efficiency of the
inverter is 89%, the low radiation losses are 5.1%. The problem of the
measurement of the inverter efficiency in case of high solar radiation has
not yet been solved.